Ashcroft GC51 - Industrial Rangeable Pressure Transmitter Bedienungsanleitung Seite 20

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 32
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 19
20
Maximum display span: OFFSET to FULL SCALE
For display mode, select “Linear display mode”
Setting item
Set min. pressure P1 as “10 psi”
Setting item
Set max. pressure P2 as “60 psi”
Setting item
Set decimal point position of linear display
as “two digit
Setting item
Set OFFSET of linear display as 0.00 ton
Setting item
Set FULL SCALE of linear display as 5.00 ton
Setting item
Set output zero point as 0.0%F.S.
(0.00ton) of max. display span
Setting item
Set output span point as 100.0%F.S.
(5.00ton) of max. display span
Setting item
2.50
Linear display and Analog
output
Linear Analog
Pressure Display Output
(psi) (ton) (mA)
60 ==> 5.00 ==> 20 Span Point
兰兰
35 ==> 2.50 ==> 12
10 ==> 0.00 ==> 4 Zero Point
ton
Seitenansicht 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 31 32

Kommentare zu diesen Handbüchern

Keine Kommentare